• The calculated residual current exceeds the value of
Gnd Op A XC GFC setting.
This setting value should exceed the highest expected single-phase earth-fault
current (calculated from phase currents). The condition is needed because the
cable current transformer saturates easily due to the high fault current.
AND
• The residual overcurrent condition must be valid at least for the duration defined
by the
Cross-country Dl GFC setting. This shows that the detection is not misled
by the high-magnitude initial transients of a single-phase earth fault.
OR
• Any phase-to-phase voltage drops below the value of the
PP voltage XC GFC
setting. The undervoltage condition is based on the fact that during a single-
phase earth fault, the phase-to-phase voltages are unaffected in isolated and
high-impedance earthed networks. The fulfilment of this criterion in combination
with the residual overcurrent condition avoids the need for any delays.
The detection of a cross-country fault is indicated by the
XC_FLT
output signal.
U
AB
U
BC
U
CA
U<
OR
I
A
+I
B
+I
C
XC_FLT
AND
I>
t
AND
EARTH_FLT = TRUE
AND
Gnd Op A XC GFC
Cross-country Dl GFC
PP voltage XC GFC
U<
U<
OR
System grounding GFC
= ”High impedance”
System grounding GFC
= ”From input”
SYS_EARTHING = TRUE
AND
OR
Figure 531: Cross-country fault detection logic for high-impedance earthed
networks
Phase preference logic for high-impedance earthed networks
The phase preference logic is applicable only in isolated and high-impedance
earthed networks. The phase preference logic for high-impedance earthed networks
is a supplement to the faulted phase identification function. It provides selective
filtering of phase-to-earth measurement elements in case of a cross-country fault or
double earth-fault in isolated and high-impedance earthed networks.
The logic releases the preferred phase-to-earth loop for measurement when a cross-
country fault with two faulted phase-to-earth loops is detected. If only one faulted
phase-to-earth loop is detected by phase selection logic (GFC), the other faulted
phase-to-earth loop is determined by analysing voltages. The phase preference
scheme must be set in the same way for the entire system so that all distance relays
measure the same preferred phase-to-earth loop. As a result, the cross-country fault
is changed into an ordinary single-phase earth-fault by selectively tripping one of
the faulted feeders.
1MRS759142 F
Protection functions
REX640
Technical Manual
957
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......