
The
Characteristic angle setting is used in the "Phase angle" mode to adjust the
operation according to the method of neutral point earthing so that in an isolated
network the
Characteristic angle (φ
RCA
) = -90° and in a compensated network φ
RCA
= 0°. In addition, the characteristic angle can be changed via the control signal
RCA_CTL. RCA_CTL affects the
Characteristic angle setting.
The
Correction angle setting can be used to improve selectivity due the inaccuracies
in the measurement transformers. The setting decreases the operation sector. The
correction can only be used with the "IoCos" or "IoSin" modes.
The polarity of the polarizing quantity can be reversed by setting the
Pol reversal to
"True", which turns the polarizing quantity by 180 degrees.
For definitions of different directional earth-fault characteristics, see
Chapter 4.2.2.9 Directional earth-fault characteristics
The
DIRECTION
output indicates on which operating sector the operating quantity
is measured. The
FAULT_DIR
output indicates in which operation sector the fault
current is measured. The output is operational once the function is started.
The directional calculation module calculates several values which are presented in
the monitored data.
Table 531: Monitored data values
Monitored data values
Description
ANGLE
Also called operating angle, shows the angle difference be-
tween the polarizing quantity (Uo, U
2
) and operating quanti-
ty (Io, I
2
).
ANGLE_RCA
The angle difference between the operating angle and Char-
acteristic angle, that is, ANGLE_RCA = ANGLE – Characteris-
tic angle.
I_OPER
The current that is used for fault detection. If the Operation
mode setting is "Phase angle", "Phase angle 80" or "Phase
angle 88", I_OPER is the measured or calculated residual
current. If the Operation mode setting is "IoSin", I_OPER is
calculated as follows I_OPER = Io x sin(ANGLE). If the Opera-
tion mode setting is "IoCos", I_OPER is calculated as follows
I_OPER = Io x cos(ANGLE).
Timer
Once activated, the timer activates the
START
output. Depending on the value of the
Operating curve type setting, the time characteristics are according to DT or IDMT.
When the operation timer has reached the value of
Operate delay time in the DT
mode or the maximum value defined by the inverse time curve, the
OPERATE
output
is activated.
When the user-programmable IDMT curve is selected, the operation time
characteristics are defined by the parameters
Curve parameter A, Curve parameter
B, Curve parameter C, Curve parameter D and Curve parameter E.
If a drop-off situation, that is, a fault suddenly disappears before the operate delay
is exceeded, the timer reset state is activated. The functionality of the timer in the
reset state depends on the combination of the
Operating curve type, Type of reset
curve and Reset delay time settings. When the DT characteristic is selected, the
reset timer runs until the set
Reset delay time value is exceeded. When the IDMT
Protection functions
1MRS759142 F
456
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......