Table 536: Reset time characteristics supported by different stages
Reset curve type
DEFLPDEF
DEFHPDEF
Note
(1) Immediate
x
x
Available for all operate time curves
(2) Def time reset
x
x
Available for all operate time curves
(3) Inverse reset
x
x
Available only for ANSI and user pro-
grammable curves
4.2.2.9
Directional earth-fault characteristics
Phase angle characteristic
The operation criterion phase angle is selected with the
Operation mode setting
using the value "Phase angle".
When the phase angle criterion is used, the
DIRECTION
output indicates on which
operating sector the operating quantity is measured. The
FAULT_DIR
output
indicates in which operation sector the fault current is measured. The output is
operational once the function is started.
The forward and reverse sectors are defined separately. The forward operation area
is limited with the
Min forward angle and Max forward angle settings. The reverse
operation area is limited with the
Min reverse angle and Max reverse angle settings.
The sector limits are always given as positive degree values.
In the forward operation area, the
Max forward angle setting gives the clockwise
sector and the
Min forward angle setting correspondingly the counterclockwise
sector, measured from the
Characteristic angle setting.
In the reverse operation area, the
Max reverse angle setting gives the clockwise
sector and the
Min reverse angle setting correspondingly the counterclockwise
sector, measured from the complement of the
Characteristic angle setting (180
degrees phase shift) .
The relay characteristic angle (RCA) is set to positive if the operating current lags
the polarizing quantity. It is set to negative if it leads the polarizing quantity.
1MRS759142 F
Protection functions
REX640
Technical Manual
465
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......