Fault indication
Fault
code
Additional
information
Fast self-
recovery
attempt
Slow 10min
self-
recovery
(# of
attempts)
Immediate
IRF-mode
Action in permanent fault
state
Internal Fault
SO-relay(s), Slot
D
-14
Runtime error:
Faulty Signal Out-
put relay(s) in card
located in slot D.
Yes
Yes (3)
No
Check wirings. Restart the
relay. If recovered by re-
starting, continue relay nor-
mal operation. If not recov-
er by restarting, exchange
the hardware module in
slot D.
Internal Fault
SO-relay(s), Slot
F
-15
Runtime error:
Faulty Signal Out-
put relay(s) in card
located in slot F.
Yes
Yes (3)
No
Check wirings. Restart the
relay. If recovered by re-
starting, continue relay nor-
mal operation. If not recov-
er by restarting, exchange
the hardware module in
slot F.
Internal Fault
SO-relay(s), Slot
G
-16
Runtime error:
Faulty Signal Out-
put relay(s) in card
located in slot G.
Yes
Yes (3)
No
Check wirings. Restart the
relay. If recovered by re-
starting, continue relay nor-
mal operation. If not recov-
er by restarting, exchange
the hardware module in
slot G.
Internal Fault
SO-relay(s), Slot
A1
-17
Runtime error:
Faulty Signal Out-
put relay(s) in card
located in slot A1.
Yes
Yes (3)
No
Check wirings. Restart the
relay. If recovered by re-
starting, continue relay nor-
mal operation. If not recov-
er by restarting, exchange
the hardware module in
slot A1.
Internal Fault
PO-relay(s), Slot
C
-20
Runtime error:
Faulty Power Out-
put relay(s) in card
located in slot C.
Yes
Yes (3)
No
Check wirings. Restart the
relay. If recovered by re-
starting, continue relay nor-
mal operation. If not recov-
er by restarting, exchange
the hardware module in
slot C.
Internal Fault
PO-relay(s), Slot
E
-21
Runtime error:
Faulty Power Out-
put relay(s) in card
located in slot E.
Yes
Yes (3)
No
Check wirings. Restart the
relay. If recovered by re-
starting, continue relay nor-
mal operation. If not recov-
er by restarting, exchange
the hardware module in
slot E.
Internal Fault
PO-relay(s), Slot
A2
-22
Runtime error:
Faulty Power Out-
put relay(s) in card
located in slot A2.
Yes
Yes (3)
No
Check wirings. Restart the
relay. If recovered by re-
starting, continue relay nor-
mal operation. If not recov-
er by restarting, exchange
the hardware module in
slot A2.
Internal Fault
PO-relay(s), Slot
B
-23
Runtime error:
Faulty Power Out-
put relay(s) in card
located in slot B
Yes
Yes (3)
No
Check wirings. Restart the
relay. If recovered by re-
starting, continue relay nor-
mal operation. If not recov-
er by restarting, exchange
the hardware module in
slot B.
Internal Fault
PO-relay(s), Slot
D
-24
Runtime error:
Faulty Power Out-
put relay(s) in card
located in slot D.
Yes
Yes (3)
No
Check wirings. Restart the
relay. If recovered by re-
starting, continue relay nor-
mal operation. If not recov-
er by restarting, exchange
the hardware module in
slot D.
Table continues on the next page
Basic functions
1MRS759142 F
104
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......