
There are two general applications which can best utilize under power factor
protection; power-factor control and loss of excitation.
When applying the function for power-factor control, both the start value and the
start reset value should be the same sign (positive/negative) as well as the same
direction (leading/lagging). Additionally, the absolute value of the start reset value
should be greater than or equal to the absolute value of the start value. This allows
the function to properly control any power factor controls within the system.
When applying the function for loss of excitation, both the start value and the start
reset value should be the same sign (positive/negative), but the directions should
be different (leading/lagging). This application is well-suited to protect against
back-spinning. In this case the start reset value will only come into play once the
system provides power in the opposite quadrant of the start value, for example,
lagging PF turns to leading PF.
4.8.4.7
Signals
MPUPF Input signals
Table 1020: MPUPF Input signals
Name
Type
Default
Description
I3P
SIGNAL
-
Three-phase currents
U3P
SIGNAL
-
Three-phase voltages
BLOCK
BOOLEAN
0=False
Block signal for acti-
vating the blocking
mode
DISABLE
BOOLEAN
0=False
Signal to block the
function during ma-
chine startup
MPUPF Output signals
Table 1021: MPUPF Output signals
Name
Type
Description
OPERATE
BOOLEAN
Operate
START
BOOLEAN
Start
ALARM
BOOLEAN
Alarm
4.8.4.8
MPUPF Settings
Table 1022: MPUPF Group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Start value Dir
1=Lagging
1=Lagging
PF direction for
start value
Table continues on the next page
1MRS759142 F
Protection functions
REX640
Technical Manual
1083
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......