
When the setting
Central PMS present is set to "No" and the Governor or AVR mode
is not Droop mode, then the function activates the binary output
GOV_DROOP
or
AVR_DROOP
by using the input
DROOP_GOV
or
DROOP_AVR
.
The governor and AVR modes can also be changed through the command
parameters
Gov mode change and AVR mode change, respectively. If the command
parameter
Gov mode change is set to "Droop" or "Fixed MW", the function activates
the binary output
GOV_DROOP
and sets integer output
MOD_CHG_GOV
to 1(“Droop”)
or 2(“Fixed MW’), respectively. If the command parameter
AVR mode change is set
to "Droop" or "Fixed MVAr", the function activates the binary output
AVR_DROOP
and
sets integer output
MOD_CHG_AVR
to 9(“Droop”) or 11(“Fixed MVAr”), respectively.
Matching for own generator CB
If the command ‘Synchronize CB’ is set to “TRUE” or input
CL_COMMAND
is TRUE, the
generator CB is selected for synchronizing. For the voltage and frequency matching
to start, the generator CB should be in open position and
Synchrocheck mode
should be set to "Asynchronous".
The measured voltage difference U_DIFF_MEAS is used for generating AVR raise
or lower pulses to match the voltages across the CB. The measured frequency
difference FR_DIFF_MEAS is used for generating governor raise or lower pulses to
match the frequencies across the CB. The voltage and frequency matching starts
only when the ENERG_STATE is “Both Live”.
Voltage difference (ΔU) = U_DIFF_MEAS
Frequency difference (ΔF) = FR_DIFF_MEAS
Matching for network CB
The generator is ready for network CB matching only when the generator CB is
closed, the protection relay is in remote mode and the generator is requested for
matching from non-source function.
After receiving the acknowledgement from ASGCSYN, the autosynchronizer
coordinator function ASCGAPC gives permission to participate in the voltage and
frequency matching across the CB to be synchronized in the network. ASCGAPC
also shares the information about how many generators participate in the voltage
matching (NgV) and frequency matching (NgF). Depending on the number of
participating generators, the voltage and frequency difference is divided among
the generators.
The voltage and frequency difference calculated for generating raise or lower pulses
for AVR and governor are
Voltage difference (ΔU) = DIFF_U_ASC1 / NgV
Frequency difference (ΔF) = DIFF_F_ASC1 / NgF
The sign bit for voltage difference and frequency difference is decided based on
the data received from ASCGAPC. The calculated voltage difference and frequency
difference are available in the Monitored data view U_DIFF_NTW and FR_DIFF_NTW,
respectively.
Control functions
1MRS759142 F
1570
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......