Table 1182: Connected inputs based on the Scheme type value
Scheme type
value
Inputs connected to an output
"Intertrip"
CR_INTER_TR
"Permissive Underreach" or "Permissive Over-
reach"
CR_PRM
"Blocking"
CR_BLOCKING
Direct underreaching transfer trip scheme DUTT
The direct intertrip scheme is enabled with
Scheme type = "Intertrip".
In the direct intertrip scheme, the start signal from the underreaching zone Z1 is
connected to the
CSUR
input to create a carrier send
CS_INTER_TR
signal. The
duration of the
CSUR
input signal is prolonged by the
Carrier Min Dur setting to
ensure a sufficient duration for the
CS_INTER_TR
signal.
The local circuit breaker is directly tripped (activation of the
OPERATE
output) with
the carrier received
CS_INTER_TR
signal after a settable pick-up delay
Coordination
Time has elapsed without further local criteria.
The unblocking function (
Unblock Mode = "Permanent" and Unblock
Mode = "Time window") must not be enabled with the DUTT scheme,
as the lost guard signal results in an immediate trip of the local circuit
breaker.
The activation of the
BLOCK
input totally blocks the direct intertrip scheme. The
CS_PRM
and
OPERATE
outputs can be blocked by the
BLK_CS_OPR
input.
~
~
Z1
Z1
CB_A
CB_B
TRIP_CB_A
TRIP_CB_B
Z1_START
Bus A
Bus B
3
3
Figure 704: Simplified functional diagram of the direct intertrip scheme
Permissive underreaching transfer trip scheme PUTT
The permissive underreach scheme is enabled with
Scheme type = "Permissive
Underreach".
1MRS759142 F
Protection related functions
REX640
Technical Manual
1239
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......