
Blocking reset
All three blocking signals, that is, waveform and the second and fifth harmonic, have
a counter or time limit which holds the blocking on for a certain time after the
blocking conditions have ceased to be fulfilled. The deblocking takes place when the
counters or time have elapsed. This is a normal case of deblocking.
The blocking signals can be reset immediately if a very high differential current is
measured or if the phase difference (angle) between the compared currents is close
to zero (in normal situations, the phase difference is 180 degrees).
Biased low stage
Biasing of the current differential protection is needed since a possible appearance
of a differential current can also be due to something else than an actual fault in the
transformer (or generator).
In the case of transformer protection, there can be several reasons for the false
differential current.
• CT errors
• Varying tap changer positions (if not automatically compensated)
• Transformer no-load current
• Transformer inrush currents
• Transformer overexcitation during overvoltage situations
• Transformer overexcitation during underfrequency situations
• CT saturation at high currents passing through the transformer
The differential current caused by CT errors and tap changer position increases at
the same percentage ratio as the load current.
In the protection of generators, the false differential current can be caused by
several reasons.
• CT errors
• CT saturation at high currents flowing through the generator
Protection functions
1MRS759142 F
724
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......