Parameter
Values (Range)
Unit
Step
Default
Description
2=Phasor
phasor measure-
ment
Tuning delay
0...3600
s
1
60
Zero-sequence volt-
age trigger delay to
start control proce-
dure
V Res variation
0.10...100.00
%Un
0.01
2.00
Req. change in Uo
that calc. of net.
param. can be exe-
cuted
Tuning mode
1=Coil movement
2=Resistor switch-
ing
1=Coil movement
Method for obtain-
ing Uo variation
V Ref adaptive
mode
0=Disable
1=Enable
1=Enable
Uref adaptive mode
V Ref adaptive de-
lay
0...1000
min
1
20
Uref adaptive delay
V Res EF level
0.00...100.00
%Un
0.01
15.00
Uo level for detec-
tion of earth fault
in the network
Default position
0...1000
A
1
50
Coil default posi-
tion
V Res minimum
0.00...20.00
%Un
0.01
0.10
Minimum level for
zero-sequence volt-
age to allow coil au-
tomatic tuning
V Res maximum
0.00...150.00
%Un
0.01
10.00
Maximum level for
zero-sequence volt-
age allowed during
automatic tuning
process
Temporary damp-
ing
0=False
1=True
0=False
Resistor switching
on/off allowed dur-
ing the automatic
tuning procedure
Minimum current
0...100
A
1
0
Minimum current
of arc-suppression
coil (low operating
limit)
Maximum current
0...10000
A
1
10000
Maximum current
of arc-suppression
coil (high operating
limit)
Error position
1=Current
2=Previous
3=Default
2=Previous
Coil position in
the case error oc-
curred during the
automatic tuning
process
Pass resonance
0=False
1=True
0=False
Pass resonance en-
abled / disabled
Transient time EF
0...1000000
ms
1
5
Transient earth-
fault duration
threshold
EF mode
1=Blocked during
EF
2=Resonance
3=Tuning during EF
1=Blocked during
EF
Operation mode
during earth-fault
(alarming earth-
fault)
Resistor healthy St 0=Off
1=On
0=Off
Resistor connec-
tion status during
healthy state oper-
ation
Resistor repeats
0...100
1
0
Number of resistor
control sequence
repeats
Table continues on the next page
Control functions
1MRS759142 F
1750
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......