Parameter
Values (Range)
Unit
Step
Default
Description
drerimpedance,
PSL
Angle load area
GFC
5.0...45.0
deg
0.1
25.0
Load discrimina-
tion angle, PSL
Gnd Op current
GFC
0.00...10.00
xIn
0.01
0.10
Basic start value for
residual curr., EF-
detection function
Gnd Op A Ref GFC
0.01...10.00
xIn
0.01
0.10
Transformer neu-
tral curr. start val.,
EF-detection func-
tion
Gnd Str voltage
GFC
0.02...1.00
xUn
0.01
0.15
Residual voltage
start value, EF-de-
tection function
Gnd Op A XC GFC
0.10...10.00
xIn
0.01
0.20
Residual current
start value, XC-fault
detection function
PP voltage XC GFC
0.10...1.00
xUn
0.01
0.80
PP-voltage start
value, XC-fault de-
tection function
Directional mode
Zn1
2=Forward
3=Reverse
1=Non-directional
2=Forward
Directional mode,
zone 1
Op Mod PP loops
Zn1
0=False
1=True
0=False
Enable PP/3P-loop
measurement, zone
1
PP Op delay Mod
Zn1
0=False
1=True
1=True
Enable operate tim-
er for PP/3P-loops,
zone 1
R1 zone 1
0.00...3000.00
ohm
0.01
40.00
Positive sequence
resistive reach,
zone 1
X1 zone 1
0.00...3000.00
ohm
0.01
40.00
Positive sequence
reactive reach, zone
1
X1 reverse zone 1
0.00...3000.00
ohm
0.01
40.00
Pos. seq. reactive
reach in rev. dir.,
non-dir. zone 1
Z1 zone 1
0.01...3000.00
ohm
0.01
56.57
Positive sequence
reach, zone 1
Z1 angle zone 1
15.0...90.0
deg
0.1
45.0
Positive sequence
line angle, zone 1
Z1 reverse zone 1
0.00...3000.00
ohm
0.01
56.57
Positive sequence
reach in rev. dir.,
non-dir. zone 1
Min Ris PP Rch Zn1
0.00...100.00
ohm
0.01
30.00
Minimum resistive
reach of PP/3P-
loops, zone 1
Max Ris PP Rch Zn1 0.00...100.00
ohm
0.01
30.00
Maximum resistive
reach of PP/3P-
loops, zone 1
PP operate delay
Zn1
20...60000
ms
1
20
Time delay to oper-
ate of PP/3P-loops,
zone 1
Op Mod Gnd loops
Zn1
0=False
1=True
0=False
Enable PE-loop
measurement, zone
1
Gnd Op Dl mode
Zn1
0=False
1=True
1=True
Enable operate tim-
er for PE-loops,
zone 1
Load Comp zone 1
0=False
1=True
1=True
Enable load com-
pensation for PE-
loops, zone 1
Table continues on the next page
1MRS759142 F
Protection functions
REX640
Technical Manual
987
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......