The blinder in forward direction,
Resistive reach Fw, can be calculated according to
2
expmin
expmax
U
P
Resistive reach Fw
K
=
×
(Equation 313)
where:
P
expmax
is the maximum exporting active power
U
expmin
is minimum phase-to-phase voltage when the exporting active power occurs
K
is a security factor to ensure that the setting of
Resistive reach Fw
less than
minimal resistive load, with a recommended value 0.8.
The resistive boundary
Resistive reach Rv can be obtained in the same way as
Resistive reach Fw, but replace the maximum exporting active power P
expmax
and
the corresponding voltage U
expmin
with the maximum importing active power
P
impmax
and the corresponding voltage U
impmin
.
The
Max impedance angle and Min impedance angle are symmetric in forward and
reverse direction, these values are recommended to set the maximum possible load
angle when load active power arrives at top. A value bigger than 20° must be used.
Protection related functions
1MRS759142 F
1298
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......