Table 907: Polarizing quantities for optional directional function for earth faults in
low-impedance earthed networks
Pol quantity GFC Polarizing
quantity
Operating
quantity
Description
Zero seq. volt.
-U
0
I
0
Zero-sequence voltage polarization
Neg. seq. volt.
-U
2
I
2
Negative-sequence voltage polari-
zation
Zero seq. cur.
I
oref
I
0
Zero-sequence current polarization
Zro vol. OR cur.
-U
0
OR I
0ref
I
0
Dual polarization
The polarizing quantity is -U
0
and the operating quantity is I
0
in case of
zero-sequence voltage polarization.
The polarizing quantity is -U
2
and the operating quantity is I
2
in case of
negative-sequence polarization.
In case of zero-sequence current polarization "Zero seq. cur.", the zero-sequence
current I
0
of the protected line is the operating quantity while another reference
zero-sequence current I
0ref
is the polarizing quantity. I
0ref
, for example, could be
the current from the neutral of a power transformer. In case of zero-sequence
current polarization, the relay characteristic angle
Chr angle GFC is internally fixed
and is equal to zero degrees. The zero-sequence current direction must remain
unchanged during all network configurations and faults. Therefore, all transformer
configurations or constructions are not suitable for polarization.
In case of dual polarization "Zro vol. OR cur.", the zero-sequence voltage polarization
and zero-sequence current polarization elements are logically OR:ed. Typically, when
I
0
is high, U
0
is low, and when I
0
is low, U
0
is high. Hence the protection can benefit
from both elements as the two polarization methods complement each other. If the
zero-sequence current polarization source is switched off for service, the flexibility
is increased as the zero-sequence voltage polarization can be used.
Faulted loop phase selection
A reliable identification of a fault and faulted phases is needed to guarantee a
selective operation of the distance protection. This information is used to release
correct measuring elements of the protection zones.
In DSTPDIS, the faulted phase selection can be done in various ways and defined
with the
Phase Sel mode GFC setting.
Table 908: Supported methods for phase selection
Setting
Enumerator value
Phase Sel mode GFC
• Overcurrent
• Vol Dep Overcur
• Under impedance
• OC AND Und impedance
• The “Overcurrent” method is the basic method for identifying the faulted phases.
It can be used in applications where the fault current magnitude exceeds the load
current despite the changes in the network configuration and fault type.
Protection functions
1MRS759142 F
948
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......