
defined as the vector sum of fundamental frequency phase voltage phasors divided
by three.
(Equation 100)
When the magnitude of U
o
exceeds setting
Voltage start value, an earth fault is
detected and
EF_IND
output is set to TRUE. Setting value
Voltage start value
is given in per unit format with system nominal phase-to-earth value (U
n_PE
) as
reference.
IFPTOC supports fundamental frequency residual voltage monitoring based on
measured U
o
from open-delta winding or internally calculated U
o
derived from
connected phase-to-earth voltages.
Input
EXT_RELEASE
is alternative method for internal GFC and validity
check modules to indicate the presence of earth fault in the protected
feeder and to release the calculation of IFPTOC function. Activation of
EXT_RELEASE
will also override earth-fault validity check criterion i.e.
earth-fault current estimate is considered as valid when
EXT_RELEASE
is activated. It is therefore mandatory that
EXT_RELEASE
is based on
start of directional earth-fault detection function, such as MFADPSDE or
DEFxPDEF.
The setting
Voltage start value defines the basic sensitivity of the IFPTOC function
in terms of fault resistance. Fault detection sensitivity in terms of fault resistance
can be estimated using the equation below:
(Equation 101)
where U
PE
is the system phase-to-earth voltage [V],
I
d
is the total system damping
[A],
I
v
is the network detuning value [A] and
U
o_pu
is setting
Voltage start value in per
unit.
In compensated networks the minimum value for the setting
Voltage start value can
be easily selected based on the resonance curve calculated by the coil controller
considering different network topologies and conditions, refer to
Protection functions
1MRS759142 F
586
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......