Figure 451: Operating characteristic for the stabilized stage of the generator
differential protection function
4.3.7.6
Application
The differential protection works on the principle of calculating the differential
current at the two ends of the winding, that is, the current entering the winding
is compared to the current exiting the winding. In case of any internal fault,
the currents entering and exiting the winding are different, which results in a
differential current, which is then used as a base for generating the operating
signal. Due to this principle, the differential protection does not trip during external
faults. However, it should be noted that interturn faults in the same phase are
usually not detected unless they developed into some other kind of fault.
The short circuit between the phases of the stator windings normally causes
high fault currents. The short circuit creates a risk of damages to the insulation,
windings and stator core. The high short circuit currents cause strong current forces
which can damage other components in the machine. The short circuit can also
initiate explosion and fire. When a short circuit occurs in a machine, there is a
damage that has to be repaired. The severity and the repair time depend on the
degree of damage, which is highly dependent on the fault time. The fast fault
clearance of this fault type is of greatest importance to limit the damages and the
economic loss.
To limit the damages in connection to the stator winding short circuits, the fault
clearance time must be as short as possible (instantaneous). The fault current
contributions from both the external power system (via the machine or the block
circuit breaker) and from the machine itself must be disconnected as fast as
possible.
Protection functions
1MRS759142 F
794
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......