
(Equation 116)
where
G
oTot
= Conductance representing the total system shunt losses, i.e. losses of the
coil(s), the parallel resistor and the total network shunt losses.
|
B
oFdTot
| = The sum of absolute values of capacitive and inductive susceptances
of the protected feeder. This term represents the energy stored in the LC-
branches of the feeder. For example, if the capacitive susceptance of the feeder
equals 20A
cap
and the inductive susceptance of the distributed coils at the feeder
equal 20A
ind
, then the sum of absolute values of susceptances of the feeder
equal 40A.
|
B
oTot
| = The sum of absolute values of capacitive and inductive susceptances
of the network. This term represents the energy stored in the LC-branches of
the total network. For example if capacitive susceptance of the network equal
100A
cap
and the inductive susceptance of the central and distributed coils equal
100A
ind
, then the sum of absolute values of susceptances of the network equal
200A.
G
oFdTot
= Conductance representing the total shunt losses of protected feeder i.e.
losses of the coil(s) located at the feeder and natural shunt losses of the feeder.
• In unearthed networks
EF validity Min Curr should be selected based on
the earth-fault current of connected feeders. Value must be smaller than
the capacitive earth-fault current due to parallel feeders. Based on practical
experience, value of 3A is found to be suitable for most applications.
• In resistance earthed networks
EF validity Min Curr should be selected based on
the value of earthing resistor. Value must be smaller than the ampere value of
earthing resistor.
To adapt the earth-fault current validity determination to a possible fault direction
change during the fault, for example during manual fault location process, a cyclic
accumulation of admittance phasor can be enabled with setting
Ena cyclic reset =
“Enable”. The duration of this evaluation cycle is only few fundamental cycles so
that function can rapidly adapt to changes in fault direction. Evaluation is based
on monitoring the sign of the accumulation of admittance phasor compared with
sign of transient admittance stored at fault ignation. In case change of polarity
is detected, and duration of polarity change exceeds setting
Intr EF reset time
and a cyclic accumulation of admittance (real- or imaginary part converted into
equivalent current value) exceeds
EF validity Min Curr, the validity evaluation of
earth-fault current estimate is reset and restarted. As default, setting
Ena cyclic
reset = “Enable”.
Information about the validity of earth-fault current estimate is also
available in
Recorded data: Valid EF detection.
Magnitude of transient resistive or reactive current component used in
evaluation of earth-fault current validity is given in recorded data as
Transient Ris Comp and Transient React Comp (fundamental frequency
magnitude) and in Monitored data as
TR_RIS_COMP
and
TR_REACT_COMP
Protection functions
1MRS759142 F
596
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......