4.7.3.2
Function block
Figure 563: Function block
4.7.3.3
Functionality
The three-phase underexcitation protection function UEXPDIS is used to protect the
synchronous machine against the underexcitation or loss of excitation condition.
The protection is based on the offset-mho circular characteristics on the impedance
plane. The function calculates the apparent impedance from the machine terminal
voltages and currents. If the impedance vector enters the offset-mho circle, the
function gives the operating signal after a set definite time. The operating time
characteristics are according to definite time (DT).
This function contains a blocking functionality. It is possible to block the function
outputs, timer or the function itself.
4.7.3.4
Analog channel configuration
UEXPDIS has two analog group inputs which all must be properly configured.
Table 945: Analog inputs
Input
Description
I3P
Three-phase currents
U3P
Three-phase voltages
See the preprocessing function blocks in this document for the possible
signal sources.
There are a few special conditions which must be noted with the configuration.
Table 946: Special conditions
Condition
Description
U3P connected to real measurements
The function can work with one voltage chan-
nel connected (
Phase Sel for Z Clc
set to "A
or AB", "B or BC" or "C or CA"), if the setting
Impedance Meas mode
is set to "1Phase-to-
earth" or "1Phaseto- phase".
The function requires that at least two (the
third voltage will be derived) or all three volt-
age channels are connected if
Impedance
Meas mode
is set to "3Phase-to-earth",
"3Phase-to-phase" or "Pos sequence".
Protection functions
1MRS759142 F
1016
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......