Parameter
Values (Range)
Unit
Step
Default
Description
Min reactive power 0.01...1.00
xSn
0.01
0.05
Reactive power lim-
it below which
DE_EXCITE is acti-
vated
Max reactive power 0.10...2.00
xSn
0.01
1.00
Reactive power lim-
it above which
DE_EXCITE is acti-
vated
Expected frequen-
cy
0.95...1.05
xFn
0.01
1.00
Expected frequen-
cy of the network in
isochronous mode
F set point no load 0.10...2.00
xFn
0.01
1.00
No load frequency
of the generator for
droop characteris-
tics
Frequency droop
0.00...100.00
%Fn
0.01
5.00
Percentage fre-
quency droop from
no load to full load
U set point no load 0.10...2.00
xUn
0.01
1.00
No load voltage of
the generator
Voltage droop
0.00...100.00
%Un
0.01
10.00
Percentage voltage
droop from no load
to full load
Rack Pos no load
0.00...100.00
%
0.01
0.00
Fuel rack position
on no load
Rack Pos gain
0.01...10.00
0.01
1.00
Rate of change of
rack position from
no load to full load
Ext current no load 0.0010...1.0000
xIn
0.0005
0.0100
Excitation current
when generator is
on no load
Ext current gain
0.0100...10.0000
0.0005
1.0000
Rate of change
of excitation Curr
from no load to full
load
Table 1353: DGMGAPC Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
5=off
1=on
Operation Off / On
Total Num of Gn
1...8
1
8
Total number of
generators
Total Num of tie
1...8
1
8
Total number of tie
Reset delay time
20...15000
ms
10
100
Reset delay time
Table 1354: DGMGAPC Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Max Freq deviation 0.00...0.10
xFn
0.01
0.01
Maximum allowed
deviation in fre-
quency
Max Freq Dev Isoc
0.00...0.10
xFn
0.01
0.01
Maximum allowed
deviation in fre-
quency for isochro-
nous mode
Max Volts deviation 0.00...0.10
xUn
0.01
0.01
Maximum allowed
deviation in voltage
Max P Dev Crl
0.00...0.10
xSn
0.01
0.01
Maximum allowed
deviation in active
power for correla-
tion
Max P Dev Vot
0.00...0.10
xSn
0.01
0.01
Maximum allowed
deviation in active
power for voting
Table continues on the next page
1MRS759142 F
Condition monitoring functions
REX640
Technical Manual
1425
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......