BSTGAPC includes two alarm output signals. The
SEND_SIG_A
output signal is
updated according to the status of the sent binary signals. The
RECV_SIG_A
output
signal is updated according to the status of the received binary signals. Each
signal can be separately included or excluded from the alarm logic with a setting
parameter.
5.5.4
Operation principle
The
Signal 1...8 mode setting can be used for changing the operation of the
bidirectional signal channel. The signal channel can be disabled by setting the
corresponding parameter value to “Not in use”. When the signal channel is disabled
locally or remotely, the corresponding
RECV_SIG_1...8
signal status is always false
on both ends.
Figure 677: Functional module diagram
Binary signal send
The status of the inputs is continuously sent in the line differential protection
telegrams.
SEND_SIG_A
can be used for alarming based on the status of
SEND_SIG_1...8
. By selecting the signal mode as "In use, alarm sel.", the
sending status of the corresponding signal affects also the activation criteria of
SEND_SIG_A
. Further, in case more than one signal channels are selected into the
alarm logic, the activation criteria can be defined according to "Any of selected"
(OR) or "All of selected" (AND).
Binary signal receive
The function receives continuous binary data within the protection telegrams from
the remote end protection relay. This received binary data status is then available
as the
RECV_SIG_1...8
outputs on the local end protection relay.
RECV_SIG_A
1MRS759142 F
Protection related functions
REX640
Technical Manual
1185
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......