
When the frequency, phase angle and voltage conditions are fulfilled, the duration
of the synchronism conditions is checked to ensure that they are still met when
the condition is determined on the basis of the measured frequency and phase
difference. Depending on the circuit breaker and the closing system, the delay
between the closing signal and the circuit breaker closing is about 50...250 ms.
The selected
Closing time of CB informs the function how long the conditions
have to persist. The value covers both circuit breaker closing delay and output
type dependent delay. The synchro check function compensates for the measured
slip frequency and the circuit breaker closing delay. The closing angle advance is
calculated continuously:
Closing angle
= ∠
− ∠
(
)
° +
−
(
)
⋅
⋅
U
U
f
f
TCB
Gen
Bus
Gen
Bus
1000
360
0
°
(Equation 356)
∠ U
Bus
Measured generator voltage phase angle
∠ U
Gen
Measured bus voltage phase angle
TCB
Parameter
Closing time of CB
TCB
t
T
x
CB
PL
=
+
+
(Equation 357)
t
CB
Circuit breaker closing delay in ms
T
PL
Output type dependent delay in ms (see
x
Hardware delays between the protection relay and CB in ms; delays due to, for
example, auxiliary relays and contactors, if used
Table 1517: Typical delays for different output types
Output type
Recommended value for T
PL
Generator voltage
measurement: Non-Adaptive
Bus voltage measurement:
Non-Adaptive
Generator voltage
measurement: Adaptive
Bus voltage measurement:
Non-Adaptive
Semiconductor output (SPO) 16 ms
7 ms
Mechanical relay output
(POSP, PODP)
23 ms
13 ms
The
Minimum Syn time setting defines the minimum time for which synchro check
conditions must be simultaneously fulfilled.
ASGCSYN can be set to the bypass mode by setting the parameters
Synchrocheck mode and Live dead mode to "Off" or, alternatively, by
activating the
BYPASS
input. In the bypass mode, the synchro check
conditions are always fulfilled. Otherwise, the operation is similar to the
normal mode.
The frequency slip acceleration (ds/dt) FR_SLIP_ACCL is the average value of
frequency slip difference (Δs) calculated over a time period of 0.5 s.
1MRS759142 F
Control functions
REX640
Technical Manual
1563
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......