The main task of the current magnitude supervision module is to secure
the correct directional determination of an earth fault so that only
the faulty feeder is disconnected or generates alarms. Therefore, the
threshold value
Min operate current should be selected carefully and
should not be set too high as this can inhibit the disconnection of the
faulty feeder.
The residual current should be measured with an accurate CBCT to
minimize the measurement errors, especially phase displacement.
The parallel resistor should be kept connected during the healthy state
so that in case of a fault, earth-fault protection can immediately see
sufficient value of resistive component for operation. If the parallel
resistor is kept disconnected during the healthy state, it should be
immediately connected when the earth fault is detected. This enables
the earth-fault protection to operate without delay.
Transient detector
The Transient detector module is used for detecting transients in the residual
current and zero-sequence voltage signals. Whenever transient is detected, this
is indicated with the
PEAK_IND
output. When the number of detected transients
equals or exceeds the
Peak counter limit setting (without the function being reset,
depending on the drop-off time set with the
Reset delay time setting),
INTR_EF
output is activated. This indicates detection of restriking or intermittent earth fault
in the network.
Transient detector affects the operation of MFADPSDE (
START
and
OPERATE
outputs) when operation mode is “Intermittent EF”. For other operation modes,
(“General EF”, “Alarming EF”),
PEAK_IND
and
INTR_EF
outputs can be used for
monitoring purposes. The operation of the Transient detector is illustrated in
Several factors affect the magnitude and frequency of fault transients, such as the
fault inception angle on the voltage wave, fault location, fault resistance and the
parameters of the feeders and the supplying transformers. If the fault is permanent
(non-transient), the initial fault transient in current and voltage can be measured,
whereas the intermittent fault creates repetitive transients. The practical sensitivity
of transient detection is limited to approximately a few hundreds of ohms of fault
resistance. Therefore the application of transient detection is limited to low-ohmic
earth faults.
Transient detector is a non-directional function. Thus, if detection of
restriking or intermittent earth faults is wanted only in the faulted feeder,
the
START
and
INTR_EF
outputs must be ANDed in the configuration.
Protection functions
1MRS759142 F
568
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......