Parameter
Values (Range)
Unit
Step
Default
Description
R0 zone 5
0.00...3000.00
ohm
0.01
160.00
Zero sequence re-
sistive reach, zone
5
X0 zone 5
0.00...3000.00
ohm
0.01
160.00
Zero sequence re-
active reach, zone 5
Factor K0 zone 5
0.00...5.00
0.01
1.00
Residual compen-
sation factor mag-
nitude, zone 5
Factor K0 angle
Zn5
-179...180
deg
1
0
Residual compen-
sation factor angle,
zone 5
Min Ris Gnd Rch
Zn5
0.00...500.00
ohm
0.01
100.00
Minimum resistive
reach of PE-loops,
zone 5
Max Ris Gnd Rch
Zn5
0.00...500.00
ohm
0.01
100.00
Maximum resistive
reach of PE-loops,
zone 5
Gnd operate Dl Zn5 20...60000
ms
1
20
Time delay to op-
erate of PE-loops,
zone 5
Table 929: DSTPDIS Group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Gnd Op current 2
GFC
0.10...10.00
xIn
0.01
1.00
Res. curr. start val-
ue for slope 2, EF-
detection function
Stab slope 1 GFC
0.00...0.30
0.01
0.10
Slope 1 for res.
curr. stabilization,
EF-detection func-
tion
Stab slope 2 GFC
0.00...1.00
0.01
1.00
Slope 2 for res. cur-
rent stabilization,
EF-detection func-
tion
A Ph Stab value
GFC
1.00...10.00
xIn
0.01
2.00
Phase current start
value for slope 2,
EF-detection func-
tion
Dir mode EF GFC
1=Non-directional
2=Forward
3=Reverse
1=Non-directional
Directional mode,
earth-fault direc-
tional function
Pol quantity GFC
-1=Zro vol.OR cur.
2=Zero seq. cur.
3=Zero seq. volt.
4=Neg. seq. volt.
3=Zero seq. volt.
Polarization meth-
od, earth-fault di-
rectional function
Chr angle GFC
-179...180
deg
1
75
Characteristic an-
gle, earth-fault di-
rectional function
Max phase angle
GFC
0...90
deg
1
80
Right hand side an-
gle, earth-fault di-
rectional function
Min phase angle
GFC
0...90
deg
1
80
Left hand side an-
gle, earth-fault di-
rectional function
Cross-country Dl
GFC
0...10000
ms
10
100
Time delay for
residual current,
XC-fault detection
function
Tilt angle zone 1
-45...45
deg
1
0
Tilt angle (posi-
tive value increases
zone area), zone 1
Table continues on the next page
Protection functions
1MRS759142 F
992
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......