Figure 626: The behavior of the IDMT timer and the output ST_OVLOD
The
ST_DUR_OVLOD
output indicates the percentage ratio of the start situation and
the operation time in the Timer 1 module and is available in the monitored data
view.
The Timer 1 module is internally blocked for one second after the
capacitor bank is connected by detecting the rising edge of the
CB_CLOSED
signal. The
CB_CLOSED
signal is True when the CB position
is closed.
Alarm level detector
The Alarm level detector compares
I_PEAK_INT_x
value to
Alarm start value. If the
phase or phases in which
I_PEAK_INT_x
exceeds the setting matches the
Num of
start phases setting, the Alarm level detector module activates the Timer 2 module.
The
Num of start phases setting is a common setting for both Operate
level detector and Alarm level detector.
Timer 2
The Timer 2 characteristics are according to Definite Time (DT) .When the operation
timer has reached the value of
Alarm delay time, the
ALARM
output is activated.
If a drop-off situation happens, the timer is reset.
The Timer 2 module is internally blocked for one second after the
capacitor bank is connected by detecting the rising edge of the
Protection functions
1MRS759142 F
1114
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......