4.1.2.8
Application
DPHxPDOC is used as short-circuit protection in three-phase distribution or sub
transmission networks operating at 50 or 60 Hz.
In radial networks, phase overcurrent protection relays are often sufficient for
the short circuit protection of lines, transformers and other equipment. The
current-time characteristic should be chosen according to the common practice
in the network. It is recommended to use the same current-time characteristic
for all overcurrent protection relays in the network. This includes the overcurrent
protection of transformers and other equipment.
The phase overcurrent protection can also be used in closed ring systems as
short circuit protection. Because the setting of a phase overcurrent protection
system in closed ring networks can be complicated, a large number of fault
current calculations are needed. There are situations with no possibility to have
the selectivity with a protection system based on overcurrent protection relays in a
closed ring system.
In some applications, the possibility of obtaining the selectivity can be improved
significantly if DPHxPDOC is used. This can also be done in the closed ring
networks and radial networks with the generation connected to the remote in the
system thus giving fault current infeed in reverse direction. Directional overcurrent
protection relays are also used to have a selective protection scheme, for example
in case of parallel distribution lines or power transformers fed by the same single
source. In ring connected supply feeders between substations or feeders with two
feeding sources, DPHxPDOC is also used.
Parallel lines or transformers
When the lines are connected in parallel and if a fault occurs in one of the lines, it is
practical to have DPHxPDOC to detect the direction of the fault. Otherwise, there is
a risk that the fault situation in one part of the feeding system can de-energize the
whole system connected to the LV side.
1MRS759142 F
Protection functions
REX640
Technical Manual
359
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......