below the minimum level before
Release delay time is exceeded, the Timer reset
state is activated. If the drop-off continues for more than
Reset delay time, Timer is
deactivated.
Blocking logic
The binary input
BLOCK
can be used to block the function. The activation of the
BLOCK
input deactivates the
RELEASE
output and resets Timer.
5.14.6
Application
The three-phase power directional element function DPSRDIR improves the
possibility to obtain a selective function of the overcurrent protection in meshed
networks. DPSRDIR is used to block or release other overcurrent protection
functions.
5.14.7
Signals
5.14.7.1
DPSRDIR Input signals
Table 1213: DPSRDIR Input signals
Name
Type
Default
Description
I3P
SIGNAL
-
Three-phase currents
U3P
SIGNAL
-
Three-phase voltages
BLOCK
BOOLEAN
0=False
Block signal for acti-
vating the blocking
mode
5.14.7.2
DPSRDIR Output signals
Table 1214: DPSRDIR Output signals
Name
Type
Description
RELEASE
BOOLEAN
Release signal if direction cri-
teria is satisified
DIRECTION
Enum
Direction information
5.14.8
DPSRDIR Settings
Table 1215: DPSRDIR Group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Release delay time
0...1000
ms
1
10
Release delay time
Characteristic an-
gle
-179...180
deg
1
60
Characteristic an-
gle
Table continues on the next page
Protection related functions
1MRS759142 F
1284
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......