If
Clock number is “Clk Num 1”, “Clk Num 5”, “Clk Num 7” or “Clk Num 11”, the vector
group matching is done on one side only. A possible zero-sequence component
of the phase currents at earth faults occurring outside the protection area is
automatically eliminated in the numerically implemented delta connection before
the differential current and the biasing current are calculated. This is why the vector
group matching is almost always made on the star connected side of the “Ynd” and
“Dyn” connected transformers.
If
Clock number is “Clk Num 0” or “Clk Num 6”, the zero-sequence component of
the phase currents is not eliminated automatically on either side. Therefore, the
zero-sequence component on the star connected side that is earthed at its star
point has to be eliminated by using the Zro A elimination parameter.
The same parameter has to be used to eliminate the zero-sequence component
if there is, for example, an earthing transformer on the delta-connected side of
the “Ynd” power transformer in the area to be protected. In this case, the vector
group matching is normally made on the side of the star connection. On the side
of the delta connection, the elimination of the zero-sequence component has to be
eliminated by using the Zro A elimination parameter.
By using the Zro A elimination parameter, the zero-sequence component of the local
phase currents is calculated and reduced for each phase current:
I
I
I
I
I
LOC
A
LOC
A
LOC
A
LOC
B
LOC
C
−
−
−
−
−
=
− ×
+
+
_
_
_
_
_
1
3
(Equation 152)
I
I
I
I
I
LOC
B
LOC
B
LOC
A
LOC
B
LOC
C
−
−
−
−
−
=
− ×
+
+
_
_
_
_
_
1
3
(Equation 153)
I
I
I
I
I
LOC
C
LOC
C
LOC
A
LOC
B
LOC
C
−
−
−
−
−
=
− ×
+
+
_
_
_
_
_
1
3
Fail safe function
To prevent malfunction during communication interference, the operation of
LNPLDF is blocked when the protection communication supervision detects severe
interference in the communication channel. The timer reset stage is activated in
case the stabilized stage is started during a communication interruption. The
protection communication supervison is connected internally from PCSITPC to
LNPLDF (dotted OK line).
Protection functions
1MRS759142 F
660
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......