Table 1343: Correlation algorithm for detecting fueling faults
Type of fault
Governor mode
Fault detection criteria
Output
activation
Over fueling
fault
GOV_MOD_ISOC =
TRUE
F > (
Expected frequency
+
Max Freq
Dev Isoc
)
AND
Local active power (P) > MAX(P1, P2, …
P8) +
Max P Dev Crl
Note: Only generators within the same
subnetwork are considered for com-
parison.
OV_FUEL_FLT
GOV_MOD_DRP =
TRUE
F >
F set point no load
– ((
Frequency
droop
*0.01) * P) +
Max Freq deviation
GOV_MOD_CDRP =
TRUE
F > F_CALC
Max Freq devia-
tion
GOV_MOD_BASE =
TRUE
P > BASE
Max P Dev Crl
Under fueling
fault
GOV_MOD_ISOC =
TRUE
F < (
Expected frequency
-
Max Freq
Dev Isoc
)
AND
P < MIN(P1, P2, … P8) -
Max P Dev Crl
Note: Only generators within the same
subnetwork are considered for com-
parison.
UN_FUEL_FLT
GOV_MOD_DRP =
TRUE
F <
F set point no load
- ((
Frequency
droop
*0.01) * P) -
Max Freq deviation
GOV_MOD_CDRP =
TRUE
F < F_CALC_LIMIT -
Max Freq deviation
GOV_MOD_BASE =
TRUE
P < BASE_P_SET -
Max P Dev Crl
Voting algorithm:
Voting algorithm is applied to groups of generators running in parallel. Voting
algorithm compares the behavior of the local generator with rest of the generators
in the connected network and if the load on local generator deviates excessively
from the others, it is identified as faulty.
The algorithm needs minimum three generators (including the local generator)
running in parallel.
The algorithm can be disabled through the setting
Disable Fuel voting.
shows the method of detecting fueling faults using the voting algorithm.
Condition monitoring functions
1MRS759142 F
1412
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......