
Table 1344: Voting algorithm for detecting fueling faults
Type of fault
Fault detection criteria
Output activation
Over fueling fault
Number of generators in parallel with same gover-
nor mode >= 3
AND
MAX(P1, P2, … P8) – MIN(P1, P2 … P8) <
Max P Dev
Vot
(This check ensures that the network generators,
excluding local generator, are operating with simi-
lar load)
AND
P > MAX (P1, P2… P8) +
Max P Dev Vot
(This is to check if the local generator load (P) is
deviating significantly from other generators in the
same network)
OV_FUEL_FLT
Under fueling fault Number of generators in parallel with same gover-
nor mode >= 3
AND
MAX(P1, P2, … P8) – MIN(P1, P2 … P8) <
Max P Dev
Vot
AND
P < MIN (P1, P2… P8) -
Max P Dev Vot
UN_FUEL_FLT
If the generator is identified as faulty by the Correlation algorithm, then the
generator is removed from the Voting algorithm. Similarly if a network generator
is communicated to be faulty via inputs
GEN1_DATA … GEN8_DATA
, or if the quality
of any of the inputs
GEN1_DATA … GEN8_DATA
is unreliable, then that generator
is also removed from the Voting algorithm. This prevents misdiagnosis by Voting
algorithm in the event that several generators should suffer from a common mode
failure.
Excitation fault detection
This module detects problems with the generator excitation or AVR, which result
in excessive reactive power (over excitation) or insufficient reactive power (under
excitation) production by the generator.
As in Fueling fault detection block, the excitation faults are also detected by
Correlation algorithm and Voting algorithm. The module activates
OV_EXCT_FLT
in
case of over excitation fault detection and
UN_EXCT_FLT
output in case of under
excitation fault. These two signals are available as outputs. Once an excitation fault
is detected, the module initiates the Control logic module.
If the input
AVR_MODE_DRP
is FALSE, indicating that the automatic voltage regulator
is not in droop mode, then the module is disabled. If the quality status of the
local reactive power input is faulty, then the module is disabled and
INT_BLKD
output is activated. If generator present in the same subnetwork is faulty or if
the quality status of reactive power of a generator is faulty, then that generator
is removed from comparison in the Fueling fault detection module.
INT_BLKD_STS
1MRS759142 F
Condition monitoring functions
REX640
Technical Manual
1413
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......