
The function calculates the positive sequence impedance. Calculation is based on
fundamental frequency components of positive sequence current and voltage. If
the measured impedance stays between inner and outer characteristic longer than
predetermined time and moves farther inside the inner characteristic, then a power
swing condition is indicated.
4.7.6.4
Analog channel configuration
DSTRPSB has two analog group inputs which must be properly configured.
Table 980: Analog Inputs
Input
Description
I3P
Three-phase currents
U3P
Three-phase voltages
There are a few special conditions which must be noted with the configuration.
Table 981: Special conditions
Condition
Description
U3P connected to real measurements
The function can work with any two voltage
channels connected but it is recommended
to connect all three voltage channels.
4.7.6.5
Operation principle
The
Operation setting is used to enable or disable the function. When selected "On"
the function is enabled and respectively "Off" means function is disabled.
The operation of DSTRPSB can be described by using a module diagram (see figure
below). All the modules in the diagram are explained in the next sections.
BLOCK
PSB
Power
swing
detection
Impedance
calculation
I
2
U
1
SWING_ST
U3P
I3P
I
1
Figure 584: Function module diagram
Impedance calculation
This module receives positive sequence voltage which is calculated from
fundamental frequency three phase voltages and positive sequence current
calculated respectively from fundamental frequency three phase currents. For the
module to calculate impedance it is required that the positive-sequence current is
above 0.1xIn.
Operation is based on positive sequence impedance (Z
1
) which is calculated using
positive sequence voltage and current as follows:
1MRS759142 F
Protection functions
REX640
Technical Manual
1047
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......