Restoring mode
Description
cy has exceeded the
Restore start Val
setting. The manual restoration
includes a timer with the DT characteristics. When the timer has
reached the set value of the
Restore delay time
setting, the
RESTORE
output is activated if the restoring condition still persists. If the fre-
quency drops below the
Restore start Val
setting before the
RESTORE
output is activated, the reset timer is activated. If the reset timer
reaches the value of the
Reset delay time
setting, the timer resets and
the
ST_REST
start output is deactivated.
A condition can arise where the restoring operation needs to be canceled. Activating
the
BLK_REST
input for the "Auto" or "Manual" modes cancels the restoring
operation. In the "Manual" restoring mode, the cancellation happens even if
MAN_RESTORE
is present.
Once the
RESTORE
output command is cancelled, the reactivation of
RESTORE
is
possible only after the reactivation of the
OPERATE
output, that is, when the next
load-shedding operation is detected.
Blocking logic
There are three operation modes in the blocking function. The operation modes are
controlled by the
BLOCK
input and the global setting in Configuration > System >
Blocking mode that selects the blocking mode. The
BLOCK
input can be controlled
with a binary input, a horizontal communication input or an internal signal of the
protection relay's program. The influence of the
BLOCK
input signal activation is
preselected with the
Blocking mode global setting.
The
Blocking mode setting has three blocking methods. In the "Freeze timers"
mode, the operate timer is frozen to the prevailing value, but the
OPERATE
output
is not deactivated when blocking is activated. In the "Block all" mode, the whole
function is blocked and the timers are reset. In the "Block OPERATE output" mode,
the function operates normally but the
OPERATE
,
OPR_FRQ
and
OPR_FRG
outputs are
not activated.
4.6.2.6
Application
An AC power system operates at a defined rated frequency. The nominal frequency
in most systems in the world is 50 Hz or 60 Hz. The system operation is such
that the operating frequency remains approximately at the nominal frequency value
by a small margin. The safe margin of operation is usually less than ±0.5 Hz.
The system frequency stability is one of the main concerns in the transmission
and distribution network operation and control. To protect the frequency-sensitive
electrical equipment in the network, departure from the allowed band for safe
operation should be inhibited.
Any increase in the connected load requires an increase in the real power generation
to maintain the system frequency. Frequency variations form whenever there are
system conditions that result in an unbalance between the generation and load.
The rate of change of the frequency represents the magnitude of the difference
between the load and generation. A reduction in frequency and a negative rate of
change of the frequency are observed when the load is greater than the generation,
and an increase in the frequency along with a positive rate of change of the
frequency are observed if the generation is greater than the load. The rate of
change of the frequency is used for a faster decision of load-shedding. In an
Protection functions
1MRS759142 F
934
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......