
•
Ng Seq impedance Fw can be set to 50% of the Z
1
tot magnitude of the line 1
which equals in primary ohms 60.4/2 = 30.2.
•
Ng Seq impedance Rv can be set to 50% of the Z
1
tot magnitude of the line 2.
Setting is for reverse fault in parallel line and therefore magnitude is negative.
Thus setting value is in primary ohms -60.4/2 = -30.2.
• If
Characteristic angle mode is set to “Fixed”, then the value for Characteristic
angle setting can be calculated as below.
Characteristic angle = arctan(X/R)
= arctan(60.1/12.6)
= 78.3 deg
(Equation 280)
The setting
Restrain factor is set based on the minimum unbalance loading allowed
in the power system network. In this case 10% unbalance is allowed in the given
example system, hence the
Restrain factor is set to 0.1.
Fault simulation
The phase to ground faults are simulated in the given example shown in
the relay is located at the sending end of the line1 and the output is captured for
forward and reverse direction fault.
The phase A to ground fault is applied on the line1 in the forward direction, the Z
2
value is positive as well as exceeds the
Ng seq impedance Fw setting threshold,
hence the
START
output issued, FAULT_DIR indicates the fault in the forward
direction and the
OPERATE
output will be issued after the
Operate delay time
setting has passed as shown in below
Figure 581: Phase A to ground fault on forward direction
The phase A to ground fault is applied on the line2 in the reverse direction, the
calculated Z
2
value is negative as well as lower the
Ng seq impedance Rv setting
threshold, hence the
START
output issued, FAULT_DIR indicates the fault in the
reverse direction and the
OPERATE
output will be issued after the
Operate delay
time setting has passed as shown in below
1MRS759142 F
Protection functions
REX640
Technical Manual
1043
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......