When residual voltage transfer is completed, this is indicated with
COMPL_RES
output.
Residual voltage transfer can be disabled with
DISA_RES
input.
Time delayed transfer
The time delayed transfer takes place when
Transfer delay time elapses. Following
conditions must be met for time delayed transfer:
• transfer is running
• both breakers are open
• DISA_TDLY is FALSE
• setting
Ena Time delay transfer allows transfer
• if transfer is initiated manually, then ENA_FASTONLY must be FALSE
If
DISA_RUN
input is active, transfer is not allowed to complete until input is
deactivated.
Time delayed transfer can be enabled with a setting
Ena Time delay transfer. When
time delayed transfer is completed, this is indicated with
COMPL_TDLY
output.
Time delayed transfer can be disabled with
DISA_TDLY
input.
Decoupling
Decoupling is a configurable safety feature. In case during transfer both controllable
breakers end up closed or breaker position is unknown after transfer, last closed
breaker can be set to be reopened. Opening time can be configured with
Decoupling
delay setting. If decoupling is activated, this is indicated with
CB_DECOUPL
output.
Decoupling functionality can be enabled with setting
Enable decoupling.
Enable decoupling has following modes:
• “Off”, decoupling functionality disabled
• “CB man close”, decoupling is done when both connected breakers closed. Note
that this mode does not require active transfer for the decoupling.
• “Transfer based”, decoupling is done during transfer incase both controllable
breakers end up closed after transfer
• “Both”, both operation modes are in use
Decoupling functionality can be disabled with
DISA_DECOUPL
input.
If decoupling is activated, function is set to lockout state and this is indicated with
LOCKOUT
output. Lockout state can be reset via
RST_LKOUT
input.
Command
Circuit breaker opening and closing is handled by this module based on the inputs
from transfer modes.
If feeder 2 is the standby feeder, then OPEN_CB1 is activated if:
• transfer is allowed from feeder 1 to feeder 2
• transfer is not started by CB open transfer
• transfer is running, i.e. one of more transfers are active
CLOSE_CB2 is activated if:
• transfer is allowed from feeder 1 to feeder 2
• transfer is completed, this is indicated with following signals:
Control functions
1MRS759142 F
1780
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......