Level detector
Level detector sends an enabling signal to Weak-end trip logic when the residual
voltage is above the
Residual voltage Val setting.
Echo logic
Echo logic returns the received carrier signal with the
ECHO
output when it receives
a carrier receive signal (CR) if no fault has been detected by the forward and reverse
directional residual overcurrent functions and the duration of CR is longer than
the coordination time delay (the setting
Wei Crd time). The received carrier receive
signal is also given as the
CR
output.
When the WEI logic is enabled at both feeder ends, a spurious signal
can be looped round by Echo logic. To avoid a continuous lockup of the
system, the duration of the echoed signal is limited to 200 ms.
The
ECHO
and
CR
outputs can be blocked by activating the
BLOCK
input. The
FF
,
BLK_WEI1
and
BLK_WEI2
inputs can be used to block the
ECHO
output. The
FF
input is usually connected to the functional output of the fuse failure function, and
the
BLK_WEI1
input is typically connected to the start signals of the forward and
reverse directional residual overcurrent functions in the terminal. The
BLK_WEI2
signal has an in-built 200 ms drop-off delay and is usually connected to all the fault
detection functions in the terminal except the residual overvoltage function.
Weak-end trip logic
Weak-end trip logic is activated if it receives an enable signal from Level detector
and
ECHO
output of Echo logic is activated. Then a general trip signal
OPR_WEI
is
activated. The activation of the
CB_OPEN
input blocks the tripping.
The
OPR_WEI
output can be blocked by activating the
BLOCK
input.
5.13.6
Application
Current reversal logic
When the overreaching permissive communication schemes are used in parallel
feeder applications, the current reversal can result in unselective tripping. Such a
condition can occur in the healthy feeder when the fault is cleared in the faulty
feeder. The tripping of the healthy parallel feeder can lead to losing the connection
between the two buses. To avoid this situation, the current reversal logic (transient
blocking logic) can be used.
In the current reversal condition, the relays Relay A1, Relay A2, Relay B1 and Relay
B2 can be equipped with the scheme communication logic RESCPSCH and the
permissive overreach scheme can be enabled.
A fault occurs at Feeder 1 close to bus B. Relay A2 at the healthy feeder 2 recognizes
the fault in the forward direction and sends a CS signal to Relay B2 according to the
PUTT scheme. Relay B2 does not recognize the fault in the forward direction and
hence does not send a permissive signal to Relay A2.
1MRS759142 F
Protection related functions
REX640
Technical Manual
1277
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......