The directional restraint shown in
is obtained when both
Rst offset X and
Rst offset X angle are set with negative signs.
A fault in Automatic Voltage Regulator ( AVR) or in the excitation system may cause
a total loss of excitation. A short circuit on the slip rings reduces the excitation
voltage to zero. This causes a gradual reduction of the excitation current and
eventually a loss of excitation. An open circuit in the field circuit also causes a loss of
excitation. These are typical examples which cause underexcitation in synchronous
machines. This module detects the underexcitation condition for the above cases
when the calculated impedance enters the operating characteristics.
External loss detection
The module checks the status information of the excitation system. It is activated
when the
External Los Det Ena setting is set to "Enable". The total loss of excitation
current or a failure in the excitation system is indicated by connecting the external
binary signal to the
EXT_LOS_DET
input. The Timer is enabled immediately when the
EXT_LOS_DET
input is activated.
Timer
Once activated, the Timer activates the
START
output. The time characteristic is
according to DT. When the duration of the underexcitation exceeds the set definite
Operate delay time, the
OPERATE
output is activated. If the impedance locus moves
out of the offset-mho operating characteristics before the module operates, the
reset timer is activated. If the reset timer reaches the value set by
Reset delay time,
the operating timer resets and the
START
output is deactivated.
The Timer calculates the start duration value START_DUR, which indicates the
percentage ratio of the start situation and the set operating time (DT). The value
isavailable in the Monitored data view.
Blocking logic
There are three operation modes in the blocking functionality. The operation
modes are controlled by the
BLOCK
input and the global setting Configuration >
System > Blocking mode which selects the blocking mode. The
BLOCK
input can be
controlled by a binary input, a horizontal communication input or an internal signal
of the protection relay's program. The influence of the
BLOCK
signal activation is
preselected with the global setting
Blocking mode.
The
Blocking mode setting has three blocking methods. In the "Freeze timers"
mode, the operate timer is frozen to the prevailing value. In the "Block all" mode, the
whole function is blocked and the timers are reset. In the "Block OPERATE output"
mode, the function operates normally but the
OPERATE
output is not activated.
4.7.3.6
Application
There are limits for the underexcitation of a synchronous machine. A reduction of
the excitation current weakens the coupling between the rotor and the external
power system. The machine may lose the synchronism and start to operate like an
induction machine, which increases the consumption of the reactive power. Even if
the machine does not lose synchronism, it is not recommended to operate in this
state. The underexcitation causes excessive heating in the end region of the stator
winding. This can damage the insulation of the stator winding and even the iron
core.
Protection functions
1MRS759142 F
1020
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......