current is higher than 1.0, the slope of the operation characteristic (ID/IB) is
constant at 50 percent. Different operating characteristics are possible based on
the
Operate value setting.
For the protection of the trip, the measured neutral current has to be above 4
percent. When the condition has been fulfilled, the measured neutral current must
stay above 2 percent, otherwise reset time is started.
To calculate the directional differential current ID_COSPHI, the fundamental
frequency amplitude of both the residual and neutral currents has to be above 4
percent of In. If neither or only one condition is fulfilled at a time, the cosφ term
is forced to 1. After the conditions are fulfilled, both currents must stay above 2
percent of In to allow the continuous calculation of the cosφ term.
Second harmonic blocking
This module compares the ratio of the current second harmonic (I
0
_2H) and
fundamental component of I
0
to the set value
Start value 2.H. If the ratio (I
0
_2H / I
0
) value exceeds the set value, the
BLK2H
output is activated.
The blocking also prevents unwanted operation at the recovery and sympathetic
magnetizing inrushes. At the recovery inrush, the magnetizing current of the
transformer to be protected increases momentarily when the voltage returns to
normal after the clearance of a fault outside the protected area. The sympathetic
inrush is caused by the energization of a transformer running in parallel with the
protected transformer connected to the network.
The second harmonic blocking is disabled when
Restraint mode is set to "None" and
enabled when set to "Harmonic2".
Timer
Once activated, the Timer activates the
START
output. The time characteristic is
according to DT. When the operation timer has reached the value set by
Minimum
operate time, the
OPERATE
output is activated. If the fault disappears before the
module operates, the reset timer is activated. If the reset timer reaches the value
set by
Reset delay time, the reset timer resets and the
START
output is deactivated.
The Timer calculates the start duration value START_DUR which indicates the
percentage ratio of the start situation and the set operate time. The value is
available through the Monitored data view.
Blocking logic
There are three operation modes in the blocking function. The operation modes
are controlled by the
BLOCK
input and the global setting in Configuration >
System > Blocking mode which selects the blocking mode. The
BLOCK
input can
be controlled by a binary input, a horizontal communication input or an internal
signal of the protection relay's program. The influence of the
BLOCK
signal activation
is preselected with the global setting
Blocking mode.
The
Blocking mode setting has three blocking methods. In the "Freeze timers"
mode, the operate timer is frozen to the prevailing value, but the
OPERATE
output
is not deactivated when blocking is activated. In the "Block all" mode, the whole
function is blocked and the timers are reset. In the "Block OPERATE output" mode,
the function operates normally but the
OPERATE
output is not activated. The
activation of the output of the second harmonic blocking signal
BLK2H
deactivates
the
OPERATE
output.
Protection functions
1MRS759142 F
752
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......