Fault indication
Fault
code
Additional
information
Fast self-
recovery
attempt
Slow 10min
self-
recovery
(# of
attempts)
Immediate
IRF-mode
Action in permanent fault
state
change the hardware mod-
ule in slot D.
Internal Fault
Conf. error, Slot
F
-35
Start up error: Card
in slot F is wrong
type, is missing,
does not belong
to original configu-
ration or card firm-
ware is faulty.
No
No
Yes
Check that the card in slot
F is proper type and prop-
erly installed. Then restart
the relay. If does not then
recover by restarting, it
is hardware module failure
most likely in question. Ex-
change the hardware mod-
ule in slot F.
Internal Fault
Conf. error, Slot
G
-36
Start up error: Card
in slot G is wrong
type, is missing,
does not belong
to original configu-
ration or card firm-
ware is faulty.
No
No
Yes
Check that the card in slot
G is proper type and prop-
erly installed. Then restart
the relay. If does not then
recover by restarting, it
is hardware module failure
most likely in question. Ex-
change the hardware mod-
ule in slot G.
Internal Fault
Conf. error, Slot
A1
-37
Start up error: Card
in slot A1 is wrong
type, is missing,
does not belong
to original configu-
ration or card firm-
ware is faulty.
No
No
Yes
Check that the card in slot
A1 is proper type and prop-
erly installed. Then restart
the relay. If does not then
recover by restarting, it
is hardware module failure
most likely in question. Ex-
change the hardware mod-
ule in slot A1.
Internal Fault
Card error, Slot
C
-40
Card in slot C is
faulty.
Yes
No
Yes
Exchange the hardware
module in slot C.
Internal Fault
Card error, Slot
E
-41
Card in slot E is
faulty.
Yes
No
Yes
Exchange the hardware
module in slot E.
Internal Fault
Card error, Slot
A2
-42
Card in slot A2 is
faulty.
Yes
No
Yes
Exchange the communica-
tion module in slot A2.
Internal Fault
Card error, Slot
B
-43
Card in slot B is
faulty.
Yes
No
Yes
Exchange the hardware
module in slot B.
Internal Fault
Card error, Slot
D
-44
Card in slot D is
faulty.
Yes
No
Yes
Exchange the hardware
module in slot D.
Internal Fault
Card error, Slot
F
-45
Card in slot F is
faulty.
Yes
No
Yes
Exchange the hardware
module in slot F.
Internal Fault
Card error, Slot
G
-46
Card in slot G is
faulty.
Yes
No
Yes
Exchange the hardware
module in slot G.
Internal Fault
Card error, Slot
A1
-47
Card in slot A1 is
faulty.
Yes
No
Yes
Exchange the hardware
module in slot A1.
Internal Fault
640-Prod. Li-
cense error
-62
Runtime error:
Product license er-
ror, license file is
not found or is
wrong
No
No
Yes
If SW update under Modifi-
cation Sales has been car-
ried out, redo the update. If
not recovered, contact your
nearest ABB representative
to check the next possible
corrective action.
Basic functions
1MRS759142 F
106
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......