89 with setting
Maximum earthing Ris in primary ohms i.e. the maximum earthing
resistance encountered in protected feeder.
Group
Highest allowed EPR values [V] converted into corresponding
permissible fault current, I
Fp
[A],when earth fault is automatically
disconnected within time t [sec]
a
(750 V/
Maximum earthing Ris
)/√t
b
(2000 V/
Maximum earthing Ris
)/√t
c
(3000 V/
Maximum earthing Ris
)/√t
d
(500 V/
Maximum earthing Ris
)/√t
e1
(750 V/
Maximum earthing Ris
)/√t
e2
(1000 V/
Maximum earthing Ris
)/√t
It is important to note, that:
1. Minimum effective earth-fault current magnitude (considering the effect of
Reduction factor), which must be exceeded for the function to start, is defined
with setting
EF current Str Val. It is important to set this value according to
required protection sensitivity.
2. With
IDMT stage Min Op Tm setting user can define minimum allowed operate
time for IFPTOC i.e. this is the minimum allowed operate time of IFPTOC.
3. With
IDMT stage Max Op Tm setting user can define maximum allowed operate
time for IFPTOC i.e. this is the maximum allowed operate time of IFPTOC
although IDMT timer would define slower operate time.
Parameter defining maximum earthing resistance, setting
Maximum
earthing Ris must be always set in case Operation principle = “EF current
based” and
Operating curve type = “Inverse time IEEE80” is selected.
Setting
Maximum earthing Ris is needed to scale the touch voltage
and earth potential rise requirements defined in standard IEEE80 into
corresponding earth-fault current requirements.
Setting
Reduction factor considers the fact that only part of the earth-
fault current (I
F
) will flow back through “remote” earth and introduces
earthing and touch voltages.
When
Operating curve type = “Inverse time IEEE80” is selected, then
setting
UTp multiplier is not effective.
Consider next the following example with
Operating curve type = “Inverse time
IEEE80”:
Example 3. Inverse time operation of IFPTOC, when
Operation principle = “EF-
current based” and
Operating curve type = “Inverse time IEEE80” is illustrated in
. Start value for operation is set to be 0.02*In (2 A). IFPTOC is set to have
minimum operate time 100 ms and maximum operate time of 5000 ms. Setting
IEEE
multiplier is 500 and setting Maximum earthing Ris is 10 ohms. Reduction factor =
1.0. For illustrating the operating speed requirement of protection, limits of earth
potential rise durations defined in Finnish national Electrical Safety Regulations 89
scaled the into corresponding earth-fault current requirements using the maximum
earthing resistance R
Emax
(setting
Maximum earthing Ris) encountered in protected
feeder are shown for reference.
Protection functions
1MRS759142 F
610
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......