Activation of input
TRIGG_REC
is required in case of external triggering to record
the calculated estimates for fault distance.
TRIGG_REC
should be activated during
the earth fault after the switching of the parallel resistor.
In case of internal triggering, time instances t
1
and t
2
are determined by monitoring
the change of the resistive component of Io current using admittance calculation
during the earth fault and comparing the magnitude of change to setting
Zero Ris
Curr change. Time instance t
1
is taken at least one fundamental cycle before and
t
2
at least one fundamental cycle after the change in the resistive component of Io
exceeding the start value (setting
Zero Ris Curr change). The value for setting Zero
Ris Curr change should be chosen based on the rated current value of the parallel
resistor with proper margin:
Zero Ris Curr change < Ipar_rated [A] · q
where q = 0.5–0.7
For example, if the rated current value of the parallel resistor is 10A@20kV and In =
100 A for Io channel, then
Zero Ris Curr change < 0.05–0.07xIn
Protection related functions
1MRS759142 F
1202
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......