can be used for alarming based on the status of
RECV_SIG_1...8
. By selecting
the signal mode as "In use, alarm sel.", the received status of the corresponding
signal affects the activation criteria of
RECV_SIG_A
. Further, in case more than
one signal channels are selected into the alarm logic, the activation criteria can be
defined according to "Any of selected" (OR) or "All of selected" (AND). Each signal
has also the
Pulse time 1...8 setting that defines the minimum pulse length for
RECV_SIG_1...8
. Also, in case the protection communication supervision detects
a failure in the communication, the
RECV_SIG_1...8
outputs are not set to false
sooner than the minimum pulse length defined is first ensured for each signal.
5.5.5
Application
Among with the analog data, the binary data can also be exchanged with the line
differential protection relays. The usage of the binary data is application specific
and can vary in each separate case. The demands for the speed of the binary signals
vary depending on the usage of the data. When the binary data is used as blocking
signals for the line differential protection, the transfer response is extremely high.
Binary signal interchange can be used in applications such as:
• Remote position indications
• Inter-tripping of the circuit breakers on both line ends
• Blocking of the line differential protection during transformer inrush or current
circuit supervision failure
• Protection schemes; blocking or permissive
• Remote alarming
The figure shows the overall chain to transfer binary data in an example application.
The position indication of the local circuit breaker is connected to the protection
relay's input interface and is then available for the relay configuration. The circuit
breaker position indication is connected to the first input of BSTGAPC which is used
to send information to the remote end via communication. In the remote end, this
information is handled as a remote circuit breaker open position and it is available
from the first output of BSTGAPC. This way the information can be exchanged.
Protection related functions
1MRS759142 F
1186
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......