K
Load factor
I_A, I_B and I_C
RMS value of input phase currents (Amperes)
I
rated
Rated current (Amperes)
If
Transformer type is set to “Single phase”, the denominator consists only of I
2
rated
instead of 3×I
2
rated
.
assumes that voltage is constant and tap changer position is not
considered.
For a star-delta transformer, it is recommended to use the function on
the star winding, since the circulating zero sequence currents (in case of
unbalance) cannot be measured on the delta winding of the transformer.
Transformer parameter selection
The transformer parameters are selected based on the
Parameter Sel method,
Cooling mode, Transformer type, and Transformer rating settings.
If the
Parameter Sel method setting is set to "IEC", the transformer parameters'
values are automatically selected as per the IEC 60076-7 guidelines based on
.
Table 1323: Constants based IEC guidelines
Distribution
Transformers
Medium and Large power transformers
Cooling mode
ONAN
ONAN
ONAF
OFAF
ODAF
Oil Exponent (x)
0.8
0.8
0.8
1.0
1.0
Winding Exponent (y) 1.6
1.3
1.3
1.3
2.0
Constant K11 (k
11
)
1.00
0.50
0.50
1.00
1.00
Constant K21 (k
21
)
1.00
2.00
2.00
1.30
1.00
Constant K22 (k
22
)
2.00
2.00
2.00
1.00
1.00
Oil Time Constant
(
Շ
0
) [minutes]
180
210
150
90
90
Winding Tm Constant
(
Շ
w
) [minutes]
4
10
7
7
7
If
Parameter Sel method is set to "IEEE", the constants are selected as per the IEEE
C57.91
™
-2011 standard based on
.
Table 1324: Constants based on IEEE guidelines
Distribution
Transformers
Medium and Large power transformers
Cooling mode
ONAN
ONAN
ONAF
OFAF
ODAF
Oil Exponent (x)
0.8
0.8
0.8
0.8
1.0
Winding Exponent (y) 0.8
0.8
0.9
0.9
1.0
Constant K11 (k
11
)
1.00
1.00
1.00
1.00
1.00
Table continues on the next page
1MRS759142 F
Condition monitoring functions
REX640
Technical Manual
1385
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......