parameter
Load current limit. The maximum of measurements from the current
phases is used for blocking. By default, both the automatic operation and the
manual operation are blocked (
) when the set limit is exceeded.
The blocking status can be read from the output
BLKD_I_LOD
.
Block lowering voltage
The block lowering voltage feature blocks both raise and lower voltage commands
if the measured voltage is too low to be corrected by operating the tap changer.
Such a situation can occur due to a faulty measuring circuit, an earth fault or
an overcurrent situation. By default, only the automatic (also automatic follower)
operation is blocked when the undervoltage condition is met (
operation can be adjusted with the setting parameter
Block lower voltage.
The blocking status can be read from the output
BLKD_U_UN
.
However, there is no minimum limit for the undervoltage blocking. The blocking is
allowed even if the measured voltage is not connected or it temporarily has a very
low value. There is a minimum limit for the phase angle calculation based on the
voltage phasor magnitude.
Runback raising voltage
The manual raising command is blocked if the overvoltage limit is exceeded (
). However, in the automatic operation mode, the overvoltage situation triggers
the fast lowering feature. More information can be found in
. This operation can be adjusted with the setting parameter
Runback raise V.
The blocking status can be read from the output
RNBK_U_OV
.
High Circulating Current
The circulating current value is calculated in the operation modes Negative
Reactance Principle (NRP) and Minimizing Circulating Current (MCC). Only the
automatic operation in these modes is blocked when the high circulating current is
measured (
). This operation can be adjusted with the setting parameter
Cir current limit.
The blocking status can be read from the output
BLKD_I_CIR
.
LTC_BLOCK – external block input
With the PCM600 tool configuration possibilities, a desired blocking condition can
be built by connecting an outcome to this input. The blocking status can be read
from the output
BLKD_LTCBLK
. When activated, this input blocks only the automatic
operation of the regulator by default (
). For the fully automatic modes,
the signal activation resets the timer, and the monitored data
BLKD_LTCBLK
is not
activated.
Extreme positions
This blocking function supervises the extreme positions of the tap changer. These
extreme positions can be adjusted with the setting parameters
Raise block tap and
Lower block tap. When the tap changer reaches one of these two positions, the
commands in the corresponding direction are blocked (
). It depends on
the comparison between the
Raise block tap and Lower block tap settings, which
1MRS759142 F
Control functions
REX640
Technical Manual
1719
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......