by a binary input, a horizontal communication input or an internal signal of
the protection relay's program. The influence of the
BLOCK
signal activation is
preselected with the global setting
Blocking mode.
The
Blocking mode setting has three blocking methods. In the "Freeze timers"
mode, the operation timer is frozen to the prevailing value. In the "Block all" mode,
the whole function is blocked and the timers are reset. In the "Block OPERATE
output" mode, the function operates normally but the
OPERATE
output is not
activated.
4.8.3.6
Application
Use of distributed power generating units ( PGU) is rapidly increasing due to
liberalized markets (deregulation) and the global trend to use more renewable
sources of energy. As the capacity of these generating units increase, they are
connected directly to medium voltage networks. Until recent years it had been a
practice by grid operators to disconnect the distributed power generator from the
network in case of fault in the network.
If there is a considerable loss in the power generation, it may affect the system’s
ability to recover. To ensure power system stability, various grid codes have revised
their requirements and therefore require that the distributed PGUs have to make a
contribution to network support. In case of network faults, the distributed power
generator should not be immediately disconnected from the network. Instead, as a
matter of principle, generating plants connected to the medium-voltage network
must be capable of participating in steady-state voltage control and dynamic
network support. However, if the generators stay connected, it must be ensured
that they do not take reactive power from the network because this may lead
to collapse of the grid. DQPTUV is used for detecting such situations, that is,
simultaneous undervoltage and reactive power (under excited generators) and trip
the generators.
The protection function DQPTUV is developed considering various grid codes. For
example, in the BDEW Technical Guideline “Generating Plants Connected to the
Medium-Voltage Network” (June 2008 issue, Germany), it is stated that if all three
phase-to-phase voltages at the grid connection point decrease and remain at and
below a value of 85% of the rated and if reactive power is simultaneously consumed
at the grid connection point (under-excited operation), the generating facility must
be disconnected from the network with a time delay of 0.5 s.
1MRS759142 F
Protection functions
REX640
Technical Manual
1075
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......