
0 10 20 30 40 50 60 70 80 90 100
0
10
20
30
40
50
60
70
80
90
100
Total earth fault current (A), Rf = 0 ohm
Re
si
d
ua
l v
o
lt
ag
e
(%
)
Resonance, K = 1
0 10 20 30 40 50 60 70 80 90 100
0
10
20
30
40
50
60
70
80
90
100
Total earth fault current (A), Rf = 0 ohm
Re
si
d
ua
l v
o
lt
ag
e
(%
)
Over/Under-Compensated, K = 1.2/0.8
0 10 20 30 40 50 60 70 80 90 100
0
10
20
30
40
50
60
70
80
90
100
Total earth fault current (A), Rf = 0 ohm
Re
si
d
ua
l v
o
lt
ag
e
(%
)
Unearthed
Rf = 500 ohm
Rf = 2500 ohm
Rf = 5000 ohm
Rf = 10000 ohm
Figure 292: Influence of fault resistance on the residual voltage magnitude in 10 kV
unearthed and compensated networks. The leakage resistance is assumed to be 30
times higher than the absolute value of the capacitive reactance of the network.
Parallel resistor of the compensation coil is assumed to be disconnected.
0 10 20 30 40 50 60 70 80 90100
0
10
20
30
40
50
60
70
80
90
100
Total earth fault current (A), Rf = 0 ohm
R
es
id
ua
l v
ol
ta
ge
(%
)
Resonance, K = 1
0 10 20 30 40 50 60 70 80 90100
0
10
20
30
40
50
60
70
80
90
100
Total earth fault current (A), Rf = 0 ohm
R
es
id
ua
l v
ol
ta
ge
(%
)
Over/Under-Compensated, K = 1.2/0.8
0 10 20 30 40 50 60 70 80 90 100
0
10
20
30
40
50
60
70
80
90
100
Total earth fault current (A), Rf = 0 ohm
R
es
id
ua
l v
ol
ta
ge
(%
)
Unearthed
Rf = 500 ohm
Rf = 2500 ohm
Rf = 5000 ohm
Rf = 10000 ohm
Figure 293: Influence of fault resistance on the residual voltage magnitude in 15 kV
unearthed and compensated networks. The leakage resistance is assumed to be 30
times higher than the absolute value of the capacitive reactance of the network.
Parallel resistor of the compensation coil is assumed to be disconnected.
0 10 20 30 40 50 60 70 80 90 100
0
10
20
30
40
50
60
70
80
90
100
Total earth fault current (A), Rf = 0 ohm
R
es
id
ua
l v
ol
ta
ge
(%
)
Resonance, K = 1
0 10 20 30 40 50 60 70 80 90 100
0
10
20
30
40
50
60
70
80
90
100
Total earth fault current (A), Rf = 0 ohm
R
es
id
ua
l v
ol
ta
ge
(%
)
Over/Under-Compensated, K = 1.2/0.8
0 10 20 30 40 50 60 70 80 90100
0
10
20
30
40
50
60
70
80
90
100
Total earth fault current (A), Rf = 0 ohm
R
es
id
ua
l v
ol
ta
ge
(%
)
Unearthed
Rf = 500 ohm
Rf = 2500 ohm
Rf = 5000 ohm
Rf = 10000 ohm
Figure 294: Influence of fault resistance on the residual voltage magnitude in 20 kV
unearthed and compensated networks. The leakage resistance is assumed to be 30
times higher than the absolute value of the capacitive reactance of the network.
Parallel resistor of the compensation coil is assumed to be disconnected.
Example
In a 15 kV, 50 Hz compensated network, the maximum value for Uo during
the healthy state is 10%×Uph. Maximum earth-fault current of the system is
100 A. The maximum earth-fault current of the protected feeder is 10 A (Rf
= 0 Ω). The applied active current forcing scheme uses a 15 A resistor (at
15 kV), which is connected in parallel to the coil during the fault after a 1.0
second delay.
Solution: As a start condition for the admittance-based earth-fault
protection, the internal residual overvoltage condition of EFPADM is used.
The
Voltage start value setting must be set above the maximum healthy-
state Uo of 10%×Uph with a suitable margin.
Protection functions
1MRS759142 F
510
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......