fault appears, creating a rotor winding interturn fault and causing severe magnetic
imbalance and heavy rotor vibrations that soon lead to a severe damage.
Therefore, it is essential that any occurrence of an insulation failure is detected
and that the machine is disconnected as soon as possible. Normally, the device is
tripped after a short time delay.
A 50/60 Hz voltage is injected via the injection device REK 510 to the rotor field
winding circuit of the synchronous machine as shown in
. The injected
voltage is 100 V AC via the coupling capacitors. A coupling capacitor prevents a DC
current leakage through the injection device.
Figure 298: Principle of the rotor earth-fault protection with the current injection
device
The auxiliary AC voltage forms a small charging current I
1
to flow via the coupling
capacitors, resistances of the brushes and the leakage capacitance between the
field circuit and earth. The field-to-earth capacitance C
E
affects the level of the
resulting current to an extent which is a few milliamperes during normal no-fault
operating conditions.
If an earth fault arises in the rotor field circuit, this current increases and can reach a
level of 130 mA at a fully developed earth fault (fault resistance R
E
= 0, one coupling
capacitor C
1
= 2μF is used). The integrated current transformer of the injection
device REK 510 then amplifies this current with the ratio of 1:10 to a measurable
level. MREFPTOC is used to measure this current.
An example of the measured curves with various field-to-earth leakage capacitance
values is given in
It is recommended that the alarm and operation stages of MREFPTOC are both
used. The alarm stage for giving an indication for weakly developed earth faults
with a start value setting corresponds to a 10 kΩ fault resistance with a 10-second
delay. The operation stage for a protection against fully developed earth faults with
a start value setting corresponds to a 1...2 kΩ fault resistance with a 0.5-second
delay.
The current setting values corresponding to the required operating fault
resistances can be tested by connecting an adjustable fault simulating
resistor between the excitation winding poles and the earth. Whether
only one of the coupling capacitors or both should be used in a parallel
connection should be determined on a case-by-case basis, taking into
consideration the consequences of a possibly excessive current at a
direct earth fault.
Protection functions
1MRS759142 F
518
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......