Value unit
Value minimum
Value maximum
”Dimensionless”
100
Ω
Input mode
”Resistance”
100
0
1600
Ω
Input
AI_VAL
Input minimum
Input maximum
Figure 71: Output as a ratio of the resistance range
The output scaling function:
k
=
−
−
Input maximum Input minimum
Value maximum Value minimum
(Equation 4)
f
k
= − ⋅
+
Value minimum Input minimum
(Equation 5)
AI VAL
f
k
_
=
−
Input
(Equation 6)
3.15.4.2
Limit value supervision
All the measurement inputs have individual limit supervision modules that operate
similarly as in the measurement functions. The measured values are compared
against their set value limits. The limit supervision outputs are
HIGH_ALARM
,
HIGH_WARN
,
LOW_WARN
and
LOW_ALARM
.
When an output is scaled,
Value maximum and Value minimum are the range limits
to which the output value is limited or scaled. Hysteresis is added to the range limit
values so that the output value is allowed to slightly exceed or go below the limit
value before being treated as out of range.
The pre-defined hysteresis values are set based on the set
Value unit.
Table 105: Pre-defined hysteresis values based on Value unit
Value unit
Hysteresis
Dimensionless
Based on the scaling function
1
Ampere
0.1 mA
Table continues on the next page
Basic functions
1MRS759142 F
176
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......