
4.1.4.3
Functionality
The accidental energization protection function GAEPVOC for the synchronous
generator is an overcurrent protection function which is enabled only when the
generator is at a standstill or in turning gear. The function is used to protect the
generator rotor from damage due to rapid heating.
A number of field conditions, such as generator operating errors, breaker head
flashovers, control circuit malfunctions, false actuation of breaker, or a combination
of these can cause accidental energization of the generators. The generator under
this condition suddenly causes a relatively heavy load to the surrounding network,
which might lead to power balance instability.
Since the generator starts behaving as an asynchronous motor, this three-phase
current develops higher current in the rotor, which may thermally damage the
generator in a few seconds. A very high thermal stress in both the stator winding
and the rotor has been produced by this situation.
The prime mover can also suffer from mechanical damage in moving parts like
turbine blades or gearing teeth. Lack of oil may damage the bearings as lube pumps
are not in operation when the generator is at a standstill. The turning gear oil
pumps are not in operation either and the accidental energization may significantly
damage the turning gear.
4.1.4.4
Analog channel configuration
GAEPVOC has two analog group inputs which must be properly configured.
Table 424: Analog inputs
Input
Description
I3P
Three-phase currents
U3P
Three-phase voltages
See the preprocessing function blocks in this document for the possible
signal sources.
There are a few special conditions which must be noted with the configuration.
Table 425: Special conditions
Condition
Description
U3P connected real meas-
urements
The function can work with any two voltage channels connec-
ted but it is recommended to connect all three voltage chan-
nels.
Improper analog channel configuration causes a validation error if the analog
channels are not completely configured or they do not match with certain settings.
check the contents of this chapter and also the preprocessing blocks in this
document. The configuration can be written to the protection relay once the
mismatch is corrected.
1MRS759142 F
Protection functions
REX640
Technical Manual
379
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......