reoccurs during the reset time, the operation calculation is made based on the
effects of the period when
START
was previously active. This is intended to allow an
operating condition to occur in less time to account for the heating effects from the
previous active start period.
When
START
becomes active, the reset time is based on the following equation.
reset time
START
DUR
Cooling time
=
⋅
_
100
(Equation 248)
For the IDMT curves, when
START
is deactivated, the integral value calculated during
START
is continuously decremented by a constant that causes its value to become
zero when the reset time elapses during the reset period. If a fault reoccurs, the
integration continues from the current integral value and the start time is adjusted,
as shown in
. The start time becomes the value at the time when the
fault dropped off minus the amount of reset time that occurred. If the reset period
elapses without a fault being detected, the saved values of the start time and
integration are cleared.
Figure 496: An example of a delayed reset in the inverse time characteristics.
When the start becomes active during the reset period, the operate time counter
continues from the level corresponding to the drop-off (reset time = 0.50 · Cooling
time)
Overexcitation IDMT curves 1, 2 and 3
The base equation for the IDMT curves "OvExt IDMT Crv1", "OvExt IDMT Crv2" and
"OvExt IDMT Crv3" is:
t s
e
ak b
M
c
( )
=
⋅
+ −
60
100
(Equation 249)
Protection functions
1MRS759142 F
890
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......