
Weak-end trip logic
Weak-end trip logic is activated if it receives an enable signal from Level detector
and
ECHO
output of Echo logic is activated. Then a general trip signal
OPR_WEI
is
activated. The activation of the
CB_OPEN
input blocks the tripping.
The
OPR_WEI
output can be blocked by activating the
BLOCK
input.
5.12.6
Application
Current reversal logic
In parallel feeder applications, when the overreaching permissive communication
schemes are used, unselective tripping may result due to the current reversal. Such
a condition can occur in the healthy feeder when the fault is cleared in the faulty
feeder. The tripping of the healthy parallel feeder may lead to losing the connection
between the two buses. To avoid this situation, the current reversal logic (transient
blocking logic) can be used.
Assume that Relay A1, Relay A2, Relay B1 and Relay B2 are equipped with DSOCPSCH
and the permissive overreach scheme is enabled. A fault occurs at Feeder 1 close to
bus B. Relay A2 at the healthy Feeder 2 recognizes the fault in the forward direction
within the overreaching zone Z2 and sends a CS signal to Relay B2 according to
the POTT scheme. Relay B2 does not recognize the fault in the forward direction
and does not operate even though a permissive CR signal is received from Relay A2.
Moreover, Relay B2 does not send a permissive signal to Relay A2.
Figure 719: The fault occurs at one of the parallel lines.
The faulty feeder (Feeder 1) is not simultaneously tripped at both ends and it might
occur that, for example, the circuit breaker closer to the fault at Relay B1 is tripped
faster than the breaker at bus A due to the direct operation of the zone Z1 of Relay
1MRS759142 F
Protection related functions
REX640
Technical Manual
1269
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......