
generated. The
CRL
output signal remains active until the
CRG
signal reappears.
The communication failure is not signaled by the
LCG
output.
•
Unblock Mode = "Time window": If the
CRG
signal disappears for a longer
time than defined in the
Loss of carrier time setting, the
CRL
output signal
is generated. The
CRL
output signal remains active for 150 ms, after which a
communication failure is signaled by the
LCG
output. The
LCG
output is reset
200 ms after the
CRG
signal reappears. The purpose of this mode is to ensure
tripping during a fixed delay of 150 ms after the loss of communication due
to possible consequences of an internal fault. After this time, the accelerated
tripping is allowed only if the
CR_PRM
signal is received again.
With operation modes
Unblock Mode = "Permanent" and Unblock Mode = "Time
window", the created
CRL
output signal is internally ORed with the
CR_PRM
input
to allow the permissive scheme to operate even when the communication channel
has been interrupted or lost. The
CRL
and
LCG
output signals are also available as
outputs for monitoring purposes. Activating the
BLOCK
input blocks the
CRL
and
LCG
outputs.
5.10.5
Application
To achieve fast fault clearing on the part of the protected feeder not covered by the
instantaneous zone Z1, the stepped distance protection function can be used with
DSOCPSCH.
Applying DSOCPSCH requires a communication channel capable of transmitting an
"On" or "Off" signal in each direction. To enable fast tripping, the most important
requirement for the communication channel is the communication speed.
The performance of DSOCPSCH is directly related to the communication channel
speed, and to the security against false or lost signals. Therefore, dedicated
communication channels are recommended. With short distances of up to a few
kilometers, a typical communication media is a simple pilot wire based on auxiliary
power. With distances of up to 50 km with the integrated communication interface
or up to 150 km with external equipment, fibre-optic cables using digital data
transmission can be used. To avoid false signals causing unwanted operation,
the security of the communication channel should be emphasized. Also, the
dependability of the communication channel should be considered to ensure that
the signals are reliably transmitted during the power system faults.
DSOCPSCH supports five communication schemes.
• Direct underreaching transfer trip DUTT
• Permissive underreaching transfer trip PUTT
• Permissive overreaching transfer trip POTT
• Directional comparison blocking scheme DCB
• Directional comparison unblocking scheme DCUB
Depending on whether the communication channel is used for sending a block or a
trip signal, the communication schemes can be divided into blocking schemes and
permissive schemes.
In permissive schemes, the trip signals of the distance zones are interchanged
between the terminals to receive a permission to trip during an internal fault.
The tripping of the local terminal depends on both the starting of its own
forward-looking zone and on the received signal from the opposite terminal. In
the underreaching scheme, no signals are sent during an external fault. During an
external fault, a trip signal is also sent to the opposite terminal if the fault is seen
Protection related functions
1MRS759142 F
1244
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......