Table 906: Selection of earth-fault detection criteria
Setting
Enumerator name
EF detection Mod GFC
• Io
• Io OR Uo
• Io AND Uo
• Io AND IoRef
If the residual current Io is derived from the phase currents either by the summation
connection of CTs, that is, the Holmgreen connection, or by internally summing
the phase currents, there is a risk of a false earth-fault detection due to apparent
residual current from the current transformer errors. This risk can be eliminated
using a stabilized residual current measurement. The stabilization is enabled by
setting the
EF Cur stabilization setting to "True". The stabilization increases the
residual current
Gnd Op current GFC threshold setting when the maximum phase
current exceeds the nominal current. The increase is defined with the
Stab slope
1 GFC setting. The apparent residual current may exist during short circuits and
in inrush current situations if the CTs saturate partially. The earth-fault detection
function takes the CT saturation into account with additional stabilization settings
Gnd Op current 2 GFC, A Ph Stab value GFC and Stab slope 2 GFC.
Setting
EF Cur stabilization to "False" disables the stabilization of the residual
current measurement and should be used only when the residual current is
measured with a cable current transformer. The residual current threshold setting
for earth-fault detection is
Gnd Op current GFC. If the residual current is measured
from a transformer neural point,
Gnd Op A Ref GFC is used. This is valid when the
setting
EF detection Mod GFC is "Io AND IoRef".
3I
0
/I
n
Stab slope 1 GFC
A Ph Stab value GFC
I
maxPh
/I
n
Stab slope 2 GFC
Blocking
due to CT
saturation
Blocking due
to CT errors
1.0
Gnd Op current GFC
Gnd Op current 2 GFC
Figure 526: Stabilized residual current measurement for earth-fault detection
The residual voltage can also be used as a complementary criterion for earth-fault
detection. This is valid when the setting
EF detection Mod GFC is "Io OR Uo" or EF
detection Mod GFC is "Io AND Uo". The threshold setting for the residual voltage is
Gnd Str voltage GFC.
Protection functions
1MRS759142 F
946
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......