Parameter
Values (Range)
Unit
Step
Default
Description
Conductance for-
ward
-500.00...500.00
mS
0.01
1.00
Conductance
threshold in for-
ward direction
Conductance re-
verse
-500.00...500.00
mS
0.01
-1.00
Conductance
threshold in reverse
direction
Susceptance for-
ward
-500.00...500.00
mS
0.01
1.00
Susceptance
threshold in for-
ward direction
Susceptance re-
verse
-500.00...500.00
mS
0.01
-1.00
Susceptance
threshold in reverse
direction
Table 570: EFPADM Group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Conductance tilt
Ang
-30...30
deg
1
0
Tilt angle of con-
ductance boundary
line
Susceptance tilt
Ang
-30...30
deg
1
0
Tilt angle of sus-
ceptance boundary
line
Table 571: EFPADM Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
5=off
1=on
Operation Off / On
Table 572: EFPADM Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Admittance Clc
mode
1=Normal
2=Delta
1=Normal
Admittance calcula-
tion mode
Reset delay time
0...60000
ms
1
20
Reset delay time
Pol reversal
0=False
1=True
0=False
Rotate polarizing
quantity
Min operate current 0.01...1.00
xIn
0.01
0.01
Minimum operating
current
Min operate volt-
age
0.01...1.00
xUn
0.01
0.01
Minimum operating
voltage
4.2.4.10
EFPADM Monitored data
Table 573: EFPADM Monitored data
Name
Type
Values (Range)
Unit
Description
START_DUR
FLOAT32
0.00...100.00
%
Ratio of start time / op-
erate time
COND_RES
FLOAT32
-1000.00...1000.00
mS
Real part of calculated
neutral admittance
SUS_RES
FLOAT32
-1000.00...1000.00
mS
Imaginary part of cal-
culated neutral admit-
tance
EFPADM
Enum
1=on
2=blocked
3=test
4=test/blocked
Status
Protection functions
1MRS759142 F
514
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......